[CIRCUIT INTERRUPTION TECHNOLOGY INC]
SPECIFICATIONS
Electrical Ratings 3.0 - 16A @ 125/250VAC
4.0 â 16A @ 125 (UL/CUL)
Dielectric Strength 1500Vrms min
Insulation Resistance > 100M⦠min
Interrupt Capacity 125VAC, 1000A; 250VAC, 1000A
Contact Endurance 125VAC X 150% of rated current - 500 cycles
Calibration 25°C â 105% of rated current - continuously carried
25°C â 106% to 134% - may trip or not
25°C â 135% of rated current - trip within 1 hour
150% of 4A â trip within 1 hour
25°C â 200% of rated current - trip within 1 minute
Reset Manual reset
|